In-plane axial + bending (P–M interaction), in-plane shear and special boundary elements — to IS 456 + IS 13920, ACI 318 and Eurocode 2.

What it does
A free online reinforced-concrete shear-wall and core design calculator for practising structural engineers and students. Enter the wall section (length lw, thickness tw, boundary elements), the distributed and boundary reinforcement, and the factored in-plane actions (Pu, Mu, Vu); the tool treats the wall as a column-like section, builds the P–M interaction diagram by strain compatibility, plots your demand point against the envelope, checks the in-plane shear (Vc + Vs ≤ Vmax) and the special-boundary-element stress trigger, and verifies the minimum distributed reinforcement and two-curtain detailing.
The full axial-load / in-plane-moment envelope is built by strain compatibility from the distributed web steel plus boundary bars, with your factored demand overlaid — green inside the envelope, red outside.
φMn at the actual Pu is read straight off the interaction curve and asserted ≥ Mu, and an axial overload (Pu beyond the squash / φ·0.80·P0 cap) is flagged as a hard fail — not an approximate closed-form.
Concrete Vc, horizontal-steel Vs and the absolute shear cap Vmax are reported with the utilization, so you see whether to add horizontal steel or thicken the wall.
The extreme-fibre stress trigger (σ vs 0.2·fck) tells you when special boundary elements are required, and the confinement Ash and link spacing of any provided element are checked.
How it works
Enter the wall length lw, thickness tw, cover and height hw; optionally toggle enlarged / barbell boundary elements and give their length, thickness, bars and confining links.
Specify the distributed vertical (ρv) and horizontal (ρh) web reinforcement as a ratio or as bars at a spacing, choose one or two curtains, then the concrete grade fck and steel grade fy.
Axial load Pu, in-plane moment Mu and in-plane shear Vu, plus a seismic toggle that switches on the IS 13920 / §18.10 / EC8 detailing and the boundary-element trigger.
The engine returns the P–M curve and your demand point, the flexural / axial / shear utilizations, the boundary-element verdict with confinement, and the minimum-reinforcement checks — then export a code-referenced PDF or Excel.
See it in action
Standards
Every result cites the clause it came from, so a reviewer can follow the same path you did.
Ductile RC walls — 0.25 % reinforcement each way (Cl 10.1.6), two curtains when tw ≥ 200 mm or τv > 0.25·√fck (Cl 10.1.7), spacing min(lw/5, 3·tw, 450 mm) (Cl 10.1.9), and in-plane shear with τc from IS 456 Table 19 capped at τc,max of Table 20 (Cl 10.2).
Special boundary elements — required when the extreme-fibre compressive stress σ > 0.2·fck, discontinued below 0.15·fck, with confinement steel Ash.
Wall minimum reinforcement, strain-compatibility axial-flexure (Annex G) and in-plane shear — τc plus horizontal-steel Vs, with τc enhanced by axial compression (δ = 1 + 3Pu/(Ag·fck) ≤ 1.5) for non-seismic walls only.
Special structural walls — Vn = Acv(αc·λ·√f′c + ρt·fy) ≤ 0.83√f′c·Acv, the σ > 0.2·f′c boundary-element trigger and confinement Ash = 0.09·s·hc·f′c/fyt.
Cross-section axial-flexure and shear (VRd,c, VRd,s ≤ VRd,max) with EC8 confined boundary elements over the critical height.
Who it’s for
Slender RC core walls carrying gravity plus lateral (wind / seismic) load — check the in-plane P–M demand and confirm the distributed two-curtain reinforcement.
Planar shear walls resisting storey shear and overturning moment — verify the in-plane shear against the Vmax cap and whether special boundary elements are triggered.
Walls with enlarged ends or boundary columns — model the concentrated boundary bars and confirm the confinement Ash and link spacing where σ > 0.2·fck.
Toggle seismic to apply IS 13920 Cl 10 / ACI §18.10 / EC8 — minimum 0.25 % each way, spacing limits and the boundary-element stress trigger.
Plans
Sign up free to run designs. Upgrade for unlimited runs, clean reports and the advanced analyses.
| Feature | Free₹0 | Professional₹2,999/mo · 14-day free trial |
|---|---|---|
| Saved projects | 20 projects | 50 projects |
| PDF design reports | Watermarked | Clean, with your logo |
| API access | Not included | Included |
FAQ
Something else? Open RC Shear Wall / Core Designer and try it with your own numbers.
A slender wall is treated like a column section: the distributed vertical web steel (both curtains) and the concentrated boundary bars are discretised into fibre layers across the wall length lw, and the P–M interaction envelope is built by strain compatibility about the strong axis with the wall thickness tw as the width. The wall is adequate when the factored demand point (Mu, Pu) plots inside the curve and φMn at the actual Pu is at least Mu.
Special boundary elements are required (a seismic requirement) when the extreme-fibre compressive stress under factored loads, σ = Pu/Ag + Mu·c/Ig with c = lw/2, exceeds 0.2·fck (IS 13920 Cl 10.4.1 / ACI 318-19 §18.10.6.2). They may be discontinued up the wall where the stress drops below 0.15·fck. The tool reports σ, both limits and whether any provided boundary element is adequately confined.
The concrete contribution Vc is taken per code (IS 456 Table 19 τc — enhanced by axial compression only for non-seismic IS 456 walls, since IS 13920 Cl 10.2 takes τc alone — or αc·λ·√f′c·Acv for ACI), the horizontal web steel adds Vs, and the nominal shear stress is capped at τc,max from IS 456 Table 20 (IS 13920 Cl 10.2.3) or 0.83·√f′c·Acv to ACI. When the demand exceeds the cap, adding horizontal steel does not help and the wall must be thickened.
Seismic walls need at least 0.25 % distributed reinforcement in each direction (IS 13920:2016 Cl 10.1.6 / ACI §18.10.2.1 / EC8), with the bar spacing limited to min(lw/5, 3·tw, 450 mm) (Cl 10.1.9) and two curtains when the thickness is 200 mm or more or τv exceeds 0.25·√fck (Cl 10.1.7). Non-seismic walls follow the lower IS 456 Cl 32.5 / ACI §11.6 / EC2 §9.6 minima. The tool checks ρv and ρh against the governing minimum.
IS 456:2000 with IS 13920:2016 (seismic), ACI 318-19 including §18.10 for special structural walls, and Eurocode 2 (EN 1992-1-1) with EN 1998-1 (EC8). Pick the code with the pill selector; the interaction, shear, boundary-element and detailing checks and their clause references update accordingly.
Yes — the core calculator, including the in-plane P–M interaction diagram and all code checks, is free with no card required. Optional upgrades cover advanced exports and team features.
Guides
Calculate seismic base shear by the IS 1893:2016 equivalent static method: period Ta, Sa/g, Ah and Vb, with a worked 7-storey infilled frame in Zone IV.
Read · 8 minShear wall design to IS 13920 step by step: boundary-element stress trigger, P–M interaction, in-plane shear with τc,max cap, minimum steel and spacing, plus a fully worked 3000 × 250 mm M30 wall checked by hand and in software.
Read · 17 minIn-plane axial + bending (P–M interaction), in-plane shear and special boundary elements — to IS 456 + IS 13920, ACI 318 and Eurocode 2.
Free account — no card required
Sign up to save projects, export PDFs, and access all design tools.